FEATURES: Water heater in steel with double coil in porcelain-glass steel, also suitable for installation in solar systems. Simple installation High efficiency and low operating costs Fast storage with abundant and continuous supply of hot water
The WHPS BA DS water heater is conceived to enable the storage of large quantities of domestic hot water, with  the following features: Single coil exchanger steel water heater with ceramic-glass enamel internal coating  External finish in artificial leather (“sky”) CFC and HCFC-free rigid expanded polyurethane insulation layer (soft expanded polyurethane for models  800,     1000, 1500, 2000) Magnesium protection anode (models 160, 200, 300, 500, 800, 1000) Protection electrodes with electronic device (models 1500, 2000) DHW thermometer: standard for models 160, 200, 300, 500 models, pre-setting for other models (coupling  G .) Two temperature probe holders: standard for models 160, 200, 300, 500 models, pre-setting for one holder for     other models (coupling G .) Pre-set for electrical resistance with G 1 ½ coupling (models 800, 1000, 1500, 2000) Optional kit with flange and electrical resistance (models 160, 200, 300, 500 models) Front inspection flange
Characteristics
WHPS BA 200 DS
WHPS BA 300 DS
WHPS BA 500 DS
WHPS 800 DS
WHPS 1000 DS
WHPS BA 1500 DS
WHPS BA 2000 DS
Capacity
litres
200
300
500
800
1000
1500
2000
Max. operating pressure
bar
10
10
10
10
10
10 | 6
10 | 6
Max. operating temperature
  C
95
95
95
95
95
95
95
Solar coil max. temperature
  C
110
110
110
110
110
110
110
Auxiliary coil area
m
2
0.5
0.9
0.9
1.5
1.6
2
2
Solar coil area
m
2
0.7
1.4
2.1
2.5
3.4
4
4.5
Auxiliary coil output (  T 35 K)
kW
22
31.5
31.5
40
42
57
57
Solar coil output (  T 35K)
kW
22.5
44
63
70
98
120
135
Total height
mm
1330
1560
1820
1870
2120
2225
2315
External diameter
mm
610
650
760
1000
1000
1200
1400
External diameter without insulation
mm
-
-
-
800
800
1000
1200
Tilting height
mm
1465
1690
1970
2120
2250
2450
2600
Insulation thickness
mm
50
50
55
100
100
100
100
Net weight
kg
61
105
154
225
260
400
480